Emergency Lighting

Emergency Lighting Guide

Comprehensive guide to British and European standards for emergency lighting systems.

Current British & EN Standards

BS 5266-1:2025

British Standard code of practice for emergency lighting of premises — the current UK standard for emergency lighting design, installation and verification.

BS EN 1838:2024

European standard specifying the luminous requirements for emergency escape lighting and standby lighting systems in buildings.

BS EN 50172:2024

European standard covering the provision and operation of emergency escape lighting systems.

BS EN 13032-3:2024

Standard for emergency lighting — data for lighting design and calculation of emergency lighting installations.

Types of Emergency Lighting

Different areas of a building require different categories of emergency lighting, each with specific illuminance requirements defined in BS EN 1838.

Escape Route Lighting

Illuminates escape routes to ensure safe evacuation. Must provide minimum 1 lux on the centre line of escape routes.

Typical Applications:

  • Corridors
  • Stairways
  • Exits
  • Changes in direction

Open Area Lighting (Anti-Panic)

Prevents panic in large open areas by providing sufficient illumination. Minimum 0.5 lux at floor level required.

Typical Applications:

  • Large offices
  • Warehouses
  • Retail spaces
  • Assembly areas

High-Risk Task Area Lighting

Provides adequate lighting for safe shutdown of processes. Minimum 10% of normal lighting or 15 lux, whichever is greater.

Typical Applications:

  • Plant rooms
  • Control rooms
  • Medical facilities
  • Laboratory areas

Standby Lighting

Allows normal activities to continue during mains power failure. Typically 100% of normal lighting levels.

Typical Applications:

  • Operating theatres
  • Critical infrastructure
  • 24/7 operations

Where to Place Emergency Lighting

At each exit door intended to be used in an emergency
At changes of direction, intersections, and near fire alarm call points
At each change in floor level
To illuminate exit and safety signs
In windowless rooms over 8m²
Near stairs so each flight receives direct light
Near fire-fighting equipment and safety equipment
Outside and near each final exit
In toilet areas exceeding 8m² and cubicles
Maximum spacing: 2x mounting height for escape routes

Emergency Lighting System Types

Emergency lighting systems are categorised by how the luminaires operate and how power is supplied. Each type has advantages and considerations to weigh during design.

Maintained Emergency Lighting

Luminaires remain illuminated at all times, using both mains and battery power.

Advantages

  • Easy to verify operation
  • Suitable for public areas
  • Immediate activation

Considerations

  • Higher energy consumption
  • More wear on components

Non-Maintained Emergency Lighting

Luminaires only illuminate when mains power fails, operating solely on battery.

Advantages

  • Energy efficient
  • Lower running costs
  • Extended lamp life

Considerations

  • Requires regular testing
  • Not continuously visible

Sustained Emergency Lighting

Can operate in both maintained and non-maintained modes via a manual switch.

Advantages

  • Flexible operation
  • Dual mode capability
  • Cost-effective compromise

Considerations

  • More complex installation
  • Requires proper labelling

Self-Contained Systems

Individual battery backup in each luminaire. No central battery required.

Advantages

  • Simple installation
  • Flexible placement
  • No central point of failure

Considerations

  • More maintenance points
  • Individual battery management

Central Battery Systems

Single battery bank supplies multiple luminaires via sub-circuits.

Advantages

  • Centralised maintenance
  • Easier testing
  • Professional appearance

Considerations

  • Higher initial cost
  • Complex wiring
  • Single point of failure risk

Testing & Maintenance Requirements

Daily Visual Check

Check for any obvious defects or indicator lamp failures.

Monthly Function Test

Simulate mains failure for short duration (typically 30 seconds) to verify operation.

Annual Duration Test

Full 3-hour discharge test to verify battery capacity and luminaire performance.

6-Monthly Test (Optional)

Many systems recommend 6-monthly duration tests for critical applications.

Important: All emergency lighting tests must be logged in a maintenance logbook. The Regulatory Reform (Fire Safety) Order 2005 requires that adequate emergency lighting is provided and properly maintained.